The DIN Rail LED-Dimmer is a PWM driven dimmer module capable of controling up to 8 channels.


Contents

Features

DIN Rail LED-Dimmer
  • 8x LED dimmer output
  • Intensity is variable in steps or steplessly
  • 8x Binary input for external switches
  • 2x Relais output (COM, NO) switching power: 230V/5A
  • 1x RS485 via BUS connector
  • Numeric display for device address
  • Arbitrary number of modules mountable side by side
  • Easy connection of all modules with BUS connector
  • All modules can communicate via RS485
  • DIN-Rail enclosure: 6 pitch units (div)
  • Other DIN-Rail modules available
  • Input voltage: 24V DC
  • Temperature range from -10°C to +70°C





Basic Wiring

Basic Wiring DIN Rail LED-Dimmer


Railbus Registers / Sub addresses

Communication is implemented via the DIN Rail BUS Protocol. Changes done through the DIN Rail BUS Protocol are not stored persistent. Available are these registers:

Duty cycles:

Per Channel
SADR 31 - 8 7 - 0 valid values Read Write
0x11 0 Duty Cycle Channel 1 Percent (1-100) X X
0x12 0 Duty Cycle Channel 2 Percent (1-100) X X
0x13 0 Duty Cycle Channel 3 Percent (1-100) X X
0x14 0 Duty Cycle Channel 4 Percent (1-100) X X
0x21 0 Duty Cycle Channel 5 Percent (1-100) X X
0x22 0 Duty Cycle Channel 6 Percent (1-100) X X
0x23 0 Duty Cycle Channel 7 Percent (1-100) X X
0x24 0 Duty Cycle Channel 8 Percent (1-100) X X
Per Group
SADR 31 - 24 23 - 16 15 - 8 7 - 0 valid values Read Write
0x1C Duty Cycle Channel 4 Duty Cycle Channel 3 Duty Cycle Channel 2 Duty Cycle Channel 1 Percent (1-100) X X
0x2C Duty Cycle Channel 8 Duty Cycle Channel 7 Duty Cycle Channel 6 Duty Cycle Channel 5 Percent (1-100) X X
Global
SADR 31 - 8 7 - 0 valid values Read Write
0xA0 0 Duty Cycle All Channels Percent (1-100) - X

Enable:

Per Channel
SADR 31 - 1 0 valid values Read Write
0x16 0 Enable Channel 1 On/Off (1 or 0) X X
0x17 0 Enable Channel 2 On/Off (1 or 0) X X
0x18 0 Enable Channel 3 On/Off (1 or 0) X X
0x19 0 Enable Channel 4 On/Off (1 or 0) X X
0x26 0 Enable Channel 5 On/Off (1 or 0) X X
0x27 0 Enable Channel 6 On/Off (1 or 0) X X
0x28 0 Enable Channel 7 On/Off (1 or 0) X X
0x29 0 Enable Channel 8 On/Off (1 or 0) X X
Per Group
SADR 31 - 4 3 2 1 0 valid values Read Write
0x1D 0 Enable Channel 4 Enable Channel 3 Enable Channel 2 Enable Channel 1 On/Off (1 or 0) X X
0x2D 0 Enable Channel 8 Enable Channel 7 Enable Channel 6 Enable Channel 5 On/Off (1 or 0) X X
Global
SADR 31 - 8 7 6 5 4 3 2 1 0 valid values Read Write
0xA3 0 Enable

Channel 8

Enable

Channel 7

Enable

Channel 6

Enable

Channel 5

Enable

Channel 4

Enable

Channel 3

Enable

Channel 2

Enable

Channel 1

On/Off (1 or 0) X X

Relais

SADR 31 - 2 1 - 0 valid values Read Write
0x1F 0 Relais 1 On/Off/toggle (1 or 0 or 2) X X
0x2F 0 Relais 2 On/Off/toggle (1 or 0 or 2) X X
SADR 31 - 4 3 - 2 1 - 0 valid values Read Write
0xA5 0 Relais 2 Relais 1 On/Off/toggle (1 or 0 or 2) X X

Global

SADR 31 - 1 0 valid values Read Write
0xB0 0 Global Enable On/Off (1 or 0) X X

Load defaults

SADR 31 - 0 valid values Read Write
0xFD Load default values write (1F2E3D4C) - X

Common Railbus Registers

Railbus Communication Settings
SADR 31 30 29 - 0 valid values Read Write
0xFE Suppress CRNL Suppress output reserved yes or no (1 or 0) X X
Device ID and Address
SADR 31 - 8 7 - 0 valid values Read Write
0xFF Device ID Device Address - X -
0xFF - Device Address new device address - X



Downloads

Datasheet DIN Rail LED-Dimmer

Personal tools