Zum Hauptinhalt springen

DIN Rail LED-Dimmer

This product is End of Life

This product is End of Life

The DIN Rail LED-Dimmer is a PWM driven dimmer module capable of controlling up to 8 channels.

Notice​

The LED-Dimmer is currently under major Re-Design. Features will soon change most completely.

Features​

DIN Rail LED-Dimmer

  • 8x LED dimmer output
  • Intensity is variable in steps or steplessly
  • 8x Binary input for external switches
  • 2x Relais output (COM, NO) switching power: 230V/5A
  • 1x RS485 via BUS connector
  • Numeric display for device address
  • Arbitrary number of modules mountable side by side
  • Easy connection of all modules with BUS connector
  • All modules can communicate via RS485
  • DIN-Rail enclosure: 6 pitch units (div)
  • Other DIN-Rail modules available
  • Input voltage: 24V DC
  • Temperature range from -10°C to +70°C

Basic Wiring​

Basic Wiring DIN Rail LED-Dimmer

Railbus Registers / Sub addresses​

Communication is implemented via the DIN Rail BUS Protocol. Changes done through the DIN Rail BUS Protocol are not stored persistently. Available are these registers:

Duty cycles:​

Per Channel
SADRReadWrite31 - 87 - 0valid values
0x11XX0Duty Cycle Channel 1Percent (1-100)
0x12XX0Duty Cycle Channel 2Percent (1-100)
0x13XX0Duty Cycle Channel 3Percent (1-100)
0x14XX0Duty Cycle Channel 4Percent (1-100)
0x21XX0Duty Cycle Channel 5Percent (1-100)
0x22XX0Duty Cycle Channel 6Percent (1-100)
0x23XX0Duty Cycle Channel 7Percent (1-100)
0x24XX0Duty Cycle Channel 8Percent (1-100)
Per Group
SADRReadWrite31 - 2423 - 1615 - 87 - 0valid values
0x1CXXDuty Cycle Channel 4Duty Cycle Channel 3Duty Cycle Channel 2Duty Cycle Channel 1Percent (1-100)
0x2CXXDuty Cycle Channel 8Duty Cycle Channel 7Duty Cycle Channel 6Duty Cycle Channel 5Percent (1-100)
Global
SADRReadWrite31 - 87 - 0valid values
0xA0-X0Duty Cycle All ChannelsPercent (1-100)

Enable:​

Per Channel
SADRReadWrite31 - 10valid values
0x16XX0Enable Channel 1On/Off (1 or 0)
0x17XX0Enable Channel 2On/Off (1 or 0)
0x18XX0Enable Channel 3On/Off (1 or 0)
0x19XX0Enable Channel 4On/Off (1 or 0)
0x26XX0Enable Channel 5On/Off (1 or 0)
0x27XX0Enable Channel 6On/Off (1 or 0)
0x28XX0Enable Channel 7On/Off (1 or 0)
0x29XX0Enable Channel 8On/Off (1 or 0)
Per Group
SADRReadWrite31 - 43210valid values
0x1DXX0Enable Channel 4Enable Channel 3Enable Channel 2Enable Channel 1On/Off (1 or 0)
0x2DXX0Enable Channel 8Enable Channel 7Enable Channel 6Enable Channel 5On/Off (1 or 0)
Global
SADRReadWrite31 - 876543210valid values
0xA3XX0Enable

Channel 8

Enable

Channel 7

Enable

Channel 6

Enable

Channel 5

Enable

Channel 4

Enable

Channel 3

Enable

Channel 2

Enable

Channel 1

On/Off (1 or 0)

Relais​

SADRReadWrite31 - 21 - 0valid values
0x1FXX0Relais 1On/Off/toggle (1 or 0 or 2)
0x2FXX0Relais 2On/Off/toggle (1 or 0 or 2)
SADRReadWrite31 - 43 - 21 - 0valid values
0xA5XX0Relais 2Relais 1On/Off/toggle (1 or 0 or 2)

Global​

SADRReadWrite31 - 10valid values
0xB0XX0Global EnableOn/Off (1 or 0)

Load defaults​

SADRReadWrite31 - 0valid values
0xFD-XLoad default valueswrite (1F2E3D4C)

Common Railbus Registers​

Railbus Communication Settings
SADRReadWrite313029 - 0valid values
0xFEXXSuppress CRNLSuppress outputreservedyes or no (1 or 0)
Device ID and Address
SADRReadWrite31 - 87 - 0valid values
0xFFX-Device IDDevice Address-
0xFF-X-Device Addressnew device address

Downloads​

Datasheet DIN Rail LED-Dimmer