{{Achtung|Breite=80% |This site is under construction. Some links may currently not work. If you have any questions about the content of this site, please send us an [mailto:office@in-circuit.de e-mail] }} | {{Achtung|Breite=80% |This site is under construction. Some links may currently not work. If you have any questions about the content of this site, please send us an [mailto:office@in-circuit.de e-mail] }} | ||
− | The '''{{PAGENAME}}''' is a PWM driven dimmer module capable of | + | The '''{{PAGENAME}}''' is a PWM driven dimmer module capable of controlling up to 8 channels. |
Revision as of 16:38, 22 November 2013
This site is under construction. Some links may currently not work. If you have any questions about the content of this site, please send us an e-mail |
The DIN Rail LED-Dimmer is a PWM driven dimmer module capable of controlling up to 8 channels.
Contents |
Features
- 8x LED dimmer output
- Intensity is variable in steps or steplessly
- 8x Binary input for external switches
- 2x Relais output (COM, NO) switching power: 230V/5A
- 1x RS485 via BUS connector
- Numeric display for device address
- Arbitrary number of modules mountable side by side
- Easy connection of all modules with BUS connector
- All modules can communicate via RS485
- DIN-Rail enclosure: 6 pitch units (div)
- Other DIN-Rail modules available
- Input voltage: 24V DC
- Temperature range from -10°C to +70°C
Basic Wiring
Railbus Registers / Sub addresses
Communication is implemented via the DIN Rail BUS Protocol. Changes done through the DIN Rail BUS Protocol are not stored persistent. Available are these registers:
Duty cycles:
SADR | Read | Write | 31 - 8 | 7 - 0 | valid values |
---|---|---|---|---|---|
0x11 | X | X | 0 | Duty Cycle Channel 1 | Percent (1-100) |
0x12 | X | X | 0 | Duty Cycle Channel 2 | Percent (1-100) |
0x13 | X | X | 0 | Duty Cycle Channel 3 | Percent (1-100) |
0x14 | X | X | 0 | Duty Cycle Channel 4 | Percent (1-100) |
0x21 | X | X | 0 | Duty Cycle Channel 5 | Percent (1-100) |
0x22 | X | X | 0 | Duty Cycle Channel 6 | Percent (1-100) |
0x23 | X | X | 0 | Duty Cycle Channel 7 | Percent (1-100) |
0x24 | X | X | 0 | Duty Cycle Channel 8 | Percent (1-100) |
SADR | Read | Write | 31 - 24 | 23 - 16 | 15 - 8 | 7 - 0 | valid values |
---|---|---|---|---|---|---|---|
0x1C | X | X | Duty Cycle Channel 4 | Duty Cycle Channel 3 | Duty Cycle Channel 2 | Duty Cycle Channel 1 | Percent (1-100) |
0x2C | X | X | Duty Cycle Channel 8 | Duty Cycle Channel 7 | Duty Cycle Channel 6 | Duty Cycle Channel 5 | Percent (1-100) |
SADR | Read | Write | 31 - 8 | 7 - 0 | valid values |
---|---|---|---|---|---|
0xA0 | - | X | 0 | Duty Cycle All Channels | Percent (1-100) |
Enable:
SADR | Read | Write | 31 - 1 | 0 | valid values |
---|---|---|---|---|---|
0x16 | X | X | 0 | Enable Channel 1 | On/Off (1 or 0) |
0x17 | X | X | 0 | Enable Channel 2 | On/Off (1 or 0) |
0x18 | X | X | 0 | Enable Channel 3 | On/Off (1 or 0) |
0x19 | X | X | 0 | Enable Channel 4 | On/Off (1 or 0) |
0x26 | X | X | 0 | Enable Channel 5 | On/Off (1 or 0) |
0x27 | X | X | 0 | Enable Channel 6 | On/Off (1 or 0) |
0x28 | X | X | 0 | Enable Channel 7 | On/Off (1 or 0) |
0x29 | X | X | 0 | Enable Channel 8 | On/Off (1 or 0) |
SADR | Read | Write | 31 - 4 | 3 | 2 | 1 | 0 | valid values |
---|---|---|---|---|---|---|---|---|
0x1D | X | X | 0 | Enable Channel 4 | Enable Channel 3 | Enable Channel 2 | Enable Channel 1 | On/Off (1 or 0) |
0x2D | X | X | 0 | Enable Channel 8 | Enable Channel 7 | Enable Channel 6 | Enable Channel 5 | On/Off (1 or 0) |
SADR | Read | Write | 31 - 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | valid values |
---|---|---|---|---|---|---|---|---|---|---|---|---|
0xA3 | X | X | 0 | Enable
Channel 8 |
Enable
Channel 7 |
Enable
Channel 6 |
Enable
Channel 5 |
Enable
Channel 4 |
Enable
Channel 3 |
Enable
Channel 2 |
Enable
Channel 1 |
On/Off (1 or 0) |
Relais
SADR | Read | Write | 31 - 2 | 1 - 0 | valid values |
---|---|---|---|---|---|
0x1F | X | X | 0 | Relais 1 | On/Off/toggle (1 or 0 or 2) |
0x2F | X | X | 0 | Relais 2 | On/Off/toggle (1 or 0 or 2) |
SADR | Read | Write | 31 - 4 | 3 - 2 | 1 - 0 | valid values |
---|---|---|---|---|---|---|
0xA5 | X | X | 0 | Relais 2 | Relais 1 | On/Off/toggle (1 or 0 or 2) |
Global
SADR | Read | Write | 31 - 1 | 0 | valid values |
---|---|---|---|---|---|
0xB0 | X | X | 0 | Global Enable | On/Off (1 or 0) |
Load defaults
SADR | Read | Write | 31 - 0 | valid values |
---|---|---|---|---|
0xFD | - | X | Load default values | write (1F2E3D4C) |
Common Railbus Registers
SADR | Read | Write | 31 | 30 | 29 - 0 | valid values |
---|---|---|---|---|---|---|
0xFE | X | X | Suppress CRNL | Suppress output | reserved | yes or no (1 or 0) |
SADR | Read | Write | 31 - 8 | 7 - 0 | valid values |
---|---|---|---|---|---|
0xFF | X | - | Device ID | Device Address | - |
0xFF | - | X | - | Device Address | new device address |