Hardware
DIN Rail LED-Dimmer - 8 Channel LED-Dimmer Module
Features:
- 8x LED dimmer output
- Intensity is variable in 12 steps or steplessly
- 8x Binary input for external switches
- 2x Relais output (COM, NO) switching power: 230V/5A
- 1x RS485 via BUS connector
- Numeric display for device address
- Arbitrary number of modules mountable side by side
- Easy connection of all modules with BUS connector
- All modules can communicate via RS485
- DIN-Rail enclosure: 6 pitch units (div)
- Other DIN-Rail modules available
- Input voltage: 24V DC
- Temperature range from -10°C to +70°C
Railbus Registers / Sub addresses
Communication is implemented via the DIN Rail BUS Protocol. Changes done through the DIN Rail BUS Protocol are not stored persistent. Available are these registers:
Duty cycles:
SADR | 31 - 8 | 7 - 0 | values | Read | Write |
---|---|---|---|---|---|
0x11 | 0 | Duty Cycle Channel 1 | Percent (1-100) | X | X |
0x12 | 0 | Duty Cycle Channel 2 | Percent (1-100) | X | X |
0x13 | 0 | Duty Cycle Channel 3 | Percent (1-100) | X | X |
0x14 | 0 | Duty Cycle Channel 4 | Percent (1-100) | X | X |
0x21 | 0 | Duty Cycle Channel 5 | Percent (1-100) | X | X |
0x22 | 0 | Duty Cycle Channel 6 | Percent (1-100) | X | X |
0x23 | 0 | Duty Cycle Channel 7 | Percent (1-100) | X | X |
0x24 | 0 | Duty Cycle Channel 8 | Percent (1-100) | X | X |
Enable:
SADR | 31 - 1 | 0 | values | Read | Write |
---|---|---|---|---|---|
0x16 | 0 | Enable Channel 1 | On/Off (1 or 0) | X | X |
0x17 | 0 | Enable Channel 2 | On/Off (1 or 0) | X | X |
0x18 | 0 | Enable Channel 3 | On/Off (1 or 0) | X | X |
0x19 | 0 | Enable Channel 4 | On/Off (1 or 0) | X | X |
0x26 | 0 | Enable Channel 5 | On/Off (1 or 0) | X | X |
0x27 | 0 | Enable Channel 6 | On/Off (1 or 0) | X | X |
0x28 | 0 | Enable Channel 7 | On/Off (1 or 0) | X | X |
0x29 | 0 | Enable Channel 8 | On/Off (1 or 0) | X | X |
Per Group Settings:
SADR | 31 - 24 | 23 - 16 | 15 - 8 | 7 - 0 | values | Read | Write |
---|---|---|---|---|---|---|---|
0x1C | Duty Cycle Channel 4 | Duty Cycle Channel 3 | Duty Cycle Channel 2 | Duty Cycle Channel 1 | Percent (1-100) | X | X |
0x2C | Duty Cycle Channel 8 | Duty Cycle Channel 7 | Duty Cycle Channel 6 | Duty Cycle Channel 5 | Percent (1-100) | X | X |
SADR | 31 - 4 | 3 | 2 | 1 | 0 | values | Read | Write |
---|---|---|---|---|---|---|---|---|
0x1D | 0 | Enable Channel 4 | Enable Channel 3 | Enable Channel 2 | Enable Channel 1 | On/Off (1 or 0) | X | X |
0x2D | 0 | Enable Channel 8 | Enable Channel 7 | Enable Channel 6 | Enable Channel 5 | On/Off (1 or 0) | X | X |
Relais:
SADR | 31 - 2 | 1 - 0 | values | Read | Write |
---|---|---|---|---|---|
0x1F | 0 | Enable Relais 1
(1 for on, 0 for off, write 2 to toggle) |
On/Off/toggle (1 or 0 or 2) | X | X |
0x2F | 0 | Enable Relais 2
(1 for on, 0 for off, write 2 to toggle) |
On/Off/toggle (1 or 0 or 2) | X | X |
Global:
SADR | 31 - 8 | 7 - 0 | values | Read | Write |
---|---|---|---|---|---|
0xA0 | 0 | Duty Cycle All Channels | Percent (1-100) | - | X |
SADR | 31 - 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | values | Read | Write |
---|---|---|---|---|---|---|---|---|---|---|---|---|
0xA3 | 0 | Enable
Channel 8 |
Enable
Channel 7 |
Enable
Channel 6 |
Enable
Channel 5 |
Enable
Channel 4 |
Enable
Channel 3 |
Enable
Channel 2 |
Enable
Channel 1 |
On/Off (1 or 0) per Channel | X | X |
SADR | 31 - 4 | 3 - 2 | 1 - 0 | values | Read | Write |
---|---|---|---|---|---|---|
0xA5 | 0 | Enable Relais 2 | Enable Relais 1 | On/Off/toggle (1 or 0 or 2) | X | X |
SADR | 31 - 1 | 0 | values | Read | Write |
---|---|---|---|---|---|
0xB0 | 0 | Global Enable | On/Off (1 or 0) | X | X |
Load defaults:
SADR | 31 - 0 | values | Read | Write |
---|---|---|---|---|
0xFD | Load default values | write (1F2E3D4C) | - | X |
Railbus communication settings:
SADR | 31 | 30 | 29 - 0 | values | Read | Write |
---|---|---|---|---|---|---|
0xFE | Suppress CRNL | Suppress output | reserved | yes or no (1 or 0) | X | X |
Device ID and Address:
SADR | 31 - 8 | 7 - 0 | value | Read | Write |
---|---|---|---|---|---|
0xFF | Device ID | Device Address | - | X | - |
0xFF | - | Device Address | new device address | - | X |