Revision as of 19:42, 16 September 2014
Hardware
DIN Rail Relais 6I6S - 6 Chanel Relais Module
The device DIN Rail Relais 6I6S is equipped with an ATXMEGA 128µC.
Features:
- ATXMEGA 128µC
- 6x Binary input (24 - 230V AC/DC)
- 6x Relais output (COM, NO, NC), switching power: 230V/5A
- Each 1x UART for uplink and downlink
- 1x RS485 via BUS connector
- Arbitrary number of modules mountable side by side
- Easy connection of all modules with BUS connector
- All modules can communicate via UART and RS485
- DIN-Rail enclosure: 6 pitch units (div)
- Other DIN-Rail modules available
- Input voltage: 24V DC
- Tempearture range from -10°C to +70°C
Railbus Registers / Sub addresses
Communicating via the DIN Rail BUS Protocol, the DIN Rail Relais 6I6S implements two registers. Both registers have the same layout:
SADR | 31 - 22 | 21 - 16 | 15 - 6 | 5 - 0 | Commad |
---|---|---|---|---|---|
0 | 0 | DIGIN | 0 | RELAIS | R |
0 | 0 | 0 | 0 | RELAIS | W |
1 | 0 | DIGIN | 0 | RELAIS | R |
1 | 0 | 0 | 0 | RELAIS | W |
On reading, the current status of all Pins is transmitted. If the first relais is on, bit 0 is set. If the second relais is on, bit 1 is set, and so on.
On writing only the 6 lowest bits are interpreted, and the relais set accordingly.
Writing to SADR 0 sets the relais only temporary. After a power-cycle all relais will be set to their initial state. This can be set by writing to SADR 1. In this case the state is set and stored in EEProm.