DIN Rail Relais 6I6S - 6 Chanel Relais Module

DIN Rail Relais 6I6S


The device DIN Rail Relais 6I6S is equipped with an ATXMEGA 128µC.


Features:

  • ATXMEGA 128µC
  • 6x Binary input (24 - 230V AC/DC)
  • 6x Relais output (COM, NO, NC), switching power: 230V/5A
  • Each 1x UART for uplink and downlink
  • 1x RS485 via BUS connector
  • Arbitrary number of modules mountable side by side
  • Easy connection of all modules with BUS connector
  • All modules can communicate via UART and RS485
  • DIN-Rail enclosure: 6 pitch units (div)
  • Other DIN-Rail modules available
  • Input voltage: 24V DC
  • Tempearture range from -10°C to +70°C


[edit] Railbus Registers / Sub addresses

Communicating via the DIN Rail BUS Protocol, the DIN Rail Relais 6I6S implements the following registers.


[edit] Relais and IO Registers

SADR data 31-22 data 21-16 data 15-6 data 5-0 Commad
0 0 DIGIN 5-0 0 RELAIS 5-0 R
0 0 0 0 RELAIS 5-0 W
1 0 DIGIN 5-0 0 RELAIS 5-0 R
1 0 0 0 RELAIS 5-0 W

The upper 16 bit represent the inputs, the lower 16 bits are for output state. Only the each lower 6 bits are use (6I6S means 6x In and 6x Set).

On reading, the current status of all Pins is transmitted. If the first relais is on, bit 0 is set. If the second relais is on, bit 1 is set, and so on.

On writing only the 6 lowest bits are interpreted, and the relais set accordingly.

Writing to SADR 0 sets the relais only temporary. After a power-cycle all relais will be set to their initial state. This can be set by writing to SADR 1. In this case the state is set and stored in EEProm.


[edit] Common Railbus Registers

Factory Reset
SADR Read Write 31 - 0 valid values
0xFA - X special value 0x1F2E3D4C

writing the special value to this register resets all ralais to off

Railbus Baudrate
SADR Read Write 31 - 0 valid values
0xFE X X baudrate 0, 9600(0x2580), 57600(0xE100), 115200(0x1C200)

writing 0x0 results in the baudrate set to 9600b/s

Railbus Communication Settings
SADR Read Write 31 30 29 - 0 valid values
0xFE X X Suppress CRNL Suppress output reserved yes or no (1 or 0)
Device ID and Address
SADR Read Write 31 - 8 7 - 0 valid values
0xFF X - Device ID Device Address -
0xFF - X - Device Address new device address